Unitary Products Group 15
036-21311-003-A-0104
HEATING CAPACITIES - 5 TON (BHA060)
CFM
RETURN AIR CAP
1
OUTDOOR AIR TEMPERATURE,
°
F (72% RH)
°F
& KW-100 102030405060
1,500
55
MBH 19.316 23.261 27.902 33.364 39.79 47.351 56.247 66.714
KW 3.57 3.829 4.088 4.347 4.606 4.865 5.124 5.383
70
MBH 18.491 22.436 27.077 32.539 38.965 46.526 55.422 65.889
KW 4.061 4.32 4.579 4.838 5.097 5.356 5.615 5.874
80
MBH 15.362 19.307 23.948 29.41 35.836 43.397 52.293 62.76
KW 4.358 4.617 4.876 5.135 5.394 5.653 5.912 6.171
2,000
55
MBH 23.164 27.109 31.75 37.212 43.638 51.199 60.095 70.562
KW 3.624 3.883 4.142 4.401 4.66 4.919 5.178 5.437
70
MBH 22.339 26.284 30.925 36.387 42.813 50.374 59.27 69.737
KW 4.115 4.374 4.633 4.892 5.151 5.41 5.669 5.928
80
MBH 19.21 23.155 27.796 33.258 39.684 47.245 56.141 66.608
KW 4.412 4.671 4.93 5.189 5.448 5.707 5.966 6.225
2,500
55
MBH 24.796 28.741 33.382 38.844 45.27 52.831 61.727 72.194
KW 3.754 4.013 4.272 4.531 4.79 5.049 5.308 5.567
70
MBH 23.971 27.916 32.557 38.019 44.445 52.006 60.902 71.369
KW 4.245 4.504 4.763 5.022 5.281 5.54 5.799 6.058
80
MBH 20.842 24.787 29.428 34.89 41.316 48.877 57.773 68.24
KW 4.542 4.801 5.06 5.319 5.578 5.837 6.096 6.355
APPLICATION DATA
MODEL
BHA
018 024 030 036 042 048 060
MINIMUM AIR FLOW
(CFM)
COOLING 450 600 750 900 1,050 1,200 1,500
HEATING 450 600 750 900 1,050 1,200 1,500
MAXIMUM AIR FLOW
(CFM)
COOLING 750 1,000 1,250 1,500 1,750 2,000 2,500
HEATING 750 1,000 1,250 1,500 1,750 2,000 2,500
MINIMUM OPERATING TEMPERATURE IN COOLING MODE
(AMBIENT, °F)
45 45 45 45 45 45 45
MINIMUM MIXED AIR IN COOLING MODE
(RETURN AIR, DB°F/WB°F)
68 / 57 68 / 57 68 / 57 68 / 57 68 / 57 68 / 57 68 / 57
MINIMUM MIXED AIR IN HEATING MODE
(RETURN AIR, °F)
55 55 55 55 55 55 55
ADDITIONAL STATIC PRESSURE RESISTANCE
DESCRIPTION
RESISTANCE, IWG
CFM
500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000
Wet Indoor coil
0.01 0.01 0.01 0.02 0.02 0.03 0.03 0.04 0.04 0.04 0.04 0.04 0.05 0.05 0.06 0.07
Economizer
0.00 0.00 0.00 0.01 0.01 0.01 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.07 0.08 0.08
Filter/Frame Kit
0.01 0.02 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.03 0.04 0.05 0.05 0.06 0.06 0.07
Electric Heat
0.02 0.03 0.03 0.03 0.04 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.01 0.11 0.11 0.12
NOTE: 1. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
2. The pressure thru the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver
less CFM during full economizer operation.