York Champion Series - Field Wiring Diagram; Electrical Data (Basic Unit)

York Champion Series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Unitary Products Group 17
036-21311-003-A-0104
FIELD WIRING DIAGRAM
ELECTRICAL DATA
(BASIC UNIT)
REFER TO ELECTRICAL DATA
TABLES TO SIZE THE DIS
-
CONNECT
REFER TO ELECTRICAL DATA
TABLES TO SIZE THE DIS
-
CONNECT
POWER WIRING
R
G
W
R
C
YY
W 2
C
W 1
O O
G
24 VOLT TRANSFORMER
UNIT TERMINAL STRIP
THERMOSTAT
NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.25
AMPS FOR ALL MODELS.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can
causeimproper anddangerous operation. Verify proper operationafter servicing.
PROGRAMMABLE
THERMOSTAT ONLY
** = Minimum wire size of 18 AWG
wire should be used for all field
installed 24 volt wire.
**
* = Only required on units with
supplemental electric heat.
*
CONTROL WIRING
MODEL
BHA
POWER SUP-
PLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
OUTDOOR
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN. MAX. RLA LRA
018 208/230-1-60 187 253 9.0 48.0 1.1 2.6 14.9 20 20 .96 40
024 208/230-1-60 187 253 11.2 60.0 1.1 2.6 17.7 25 25 .96 40
030 208/230-1-60 187 253 12.0 73.0 1.1 2.6 18.7 25 25 .96 40
036 208/230-1-60 187 253 17.3 94.0 1.1 3.5 26.2 35 35 .96 40
042 208/230-1-60 187 253 20.5 120.0 1.1 3.5 30.2 40 40 .96 40
048 208/230-1-60 187 253 24.4 140.0 1.5 4.0 36.0 50 50 .96 40
060 208/230-1-60 187 253 28.9 165.0 1.5 7.0 44.6 60 60 .96 40
036 208/230-3-60 187 253 10.9 78.0 1.1 3.5 18.2 25 25 .96 75
042 208/230-3-60 187 253 14.1 110.0 1.1 3.5 22.2 30 30 .96 75
048 208/230-3-60 187 253 14.1 105.0 1.5 4.0 23.1 30 30 .96 75
060 208/230-3-60 187 253 16.0 125.0 1.5 7.0 28.5 40 40 .96 75
036 460-3-60 414 504 5.8 40.0 0.6 1.8 9.6 15 15 .96 75
042 460-3-60 414 504 7.1 54.0 0.6 1.8 11.2 15 15 .96 75
048 460-3-60 414 504 7.1 55.0 0.8 2.0 11.7 15 15 .96 75
060 460-3-60 414 504 8.0 67.0 0.8 3.5 14.3 20 20 .96 75
036 575-3-60 518 630 4.5 32.0 0.4 1.5 7.6 15 15 .96 75
042 575-3-60 518 630 5.8 44.0 0.4 1.5 9.1 15 15 .96 75
048 575-3-60 518 630 5.6 44.0 0.6 1.6 9.3 15 15 .96 75
060 575-3-60 518 630 6.4 50.0 0.6 2.8 11.4 15 15 .96 75
1
= Rated in accordance with ARI Standard 110, utilization range “A”.
2
= Dual element, time delay type.
ELECTRIC HEAT
CORRECTION
FACTORS
NOMINAL VOLTAGE VOLTAGE
KW CAP. MULTI
-
PLIER
240
208
230
.75
.92
480 460 .92
600 575 .92