Unitary Products Group 19
036-21311-003-A-0104
BHA
POWER
SUPPLY
COMPRESSOR
OUT
-
DOOR
FAN
MOTOR
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
ELECTRIC HEAT ACCESSORY
MINIMUM
CIRCUIT
AMPAC
-
ITY
MAX.
FUSE
SIZE
1
AMPS
MAX.
HACR
2
BREAKER
SIZE
MODEL
RLA LRA MODEL NO.
STAGE
KW
TOTAL
AMPS
036 575-3-60 4.5 32.0 0.4 1.5
2NH04501058
2NH04501558
1
1
10.0 ***
15.0 ***
9.6
14.4
19.6
25.6
20
30
20
30
042 575-3-60 5.8 44.0 0.4 1.5
2NH04501058
2NH04501558
1
1
10.0 ***
15.0 ***
9.6
14.4
21.1
27.2
25
30
25
30
048 575-3-60 5.6 44.0 0.6 1.6
2NH04501058
2NH04501558
2NH04502058
2NH04502558
1
1
2
2
10.0 ***
15.0 ***
20.0 ***
25.0 ***
9.6
14.4
19.2
24.1
21.3
27.3
33.3
39.3
25
30
35
40
25
30
35
40
060 575-3-60 6.4 50.0 0.6 2.8
2NH04501058
2NH04501558
2NP04502058
2NP04502558
1
1
2
2
10.0 ***
15.0 ***
20.0 ***
25.0 ***
9.6
14.4
19.2
24.1
23.4
29.5
35.5
41.5
25
30
40
45
25
30
40
45
1
= Dual element, time delay type. * = KW listed is for 240 volts, use table at top of page for 208 or 230 volts.
2
= Standard circuit breakers may be used in Canada and on applications ** = KW listed is for 480 volts, use table at top of page for 460 volts.
over60 amps wheretheheatersare separately fused. ***= KW listedisfor 600 volts, use tableattopof page for575volts.
ELECTRIC HEAT
CORRECTION
FACTORS
NOMINAL VOLTAGE VOLTAGE
KW CAP. MULTI
-
PLIER
240
208
230
.75
.92
480 460 .92
600 575 .92
ELECTRICAL DATA (HEAT PUMP / ELECTRIC HEAT) (CONTINUED)