JOHNSON CONTROLS
127
SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.79-O3
ISSUE DATE: 11/09/2018
2
SLOT
NO
DESCRIPTION
MOTOR 1
2305 Motor 1 Run
2306 Motor % Full Load Amps
2351
Operating Hours Since Last Motor Lubrica-
tion
2818 VSD 1 Input Power
2822 VSD 1 Output Frequency
2823 VSD 1 Output Voltage
2824 VSD 1 Phase A Output Current (RMS)
2825 VSD 1 Phase B Output Current (RMS)
184562826 VSD 1 Phase C Output Current (RMS)
2982 VSD 1 DC Bus Voltage AU
2983 VSD 1 DC Bus Voltage AL
2984 VSD 1 DC Bus Voltage BU
2985 VSD 1 DC Bus Voltage BL
2986 VSD 1 DC Bus Voltage CU
2987 VSD 1 DC Bus Voltage CL
2835 VSD 1 Phase A Heatsink Temperature
2836 VSD 1 Phase B Heatsink Temperature
2837 VSD 1 Phase C Heatsink Temperature
17414 Motor Heater On
MOTOR 2
18708 Motor 2 Run
18709 Motor % Full Load Amps
2351
Operating Hours Since Last Motor Lubrica-
tion
18754 VSD 2 Input Power
18758 VSD 2 Output Frequency
18759 VSD 2 Output Voltage
18760 VSD 2 Phase A Output Current (RMS)
18761 VSD 2 Phase B Output Current (RMS)
18762 VSD 2 Phase C Output Current (RMS)
18849 VSD 2 DC Bus Voltage AU
18850 VSD 2 DC Bus Voltage AL
18851 VSD 2 DC Bus Voltage BU
18852 VSD 2 DC Bus Voltage BL
18853 VSD 2 DC Bus Voltage CU
18854 VSD 2 DC Bus Voltage CL
18771 VSD 2 Phase A Heatsink Temperature
18772 VSD 2 Phase B Heatsink Temperature
18773 VSD 2 Phase C Heatsink Temperature
17415 Motor Heater On
SLOT
NO
DESCRIPTION
CAPACITY CONTROL
18273 Capacity Control State
18274 Active Load Limit
17734 Lead VSD Frequency Command
17739 Lead VSD Output Frequency
18365 Lead VSD Control Mode
18336 Lead Max VGD Position
18337 Lag Max VGD Position
17687 Lead PRV Command
18456 Lead PRV Position
18368 Lead PRV Control Mode
18467 Lag PRV Position
17689 HGBP Command
18366 HGBP Control Mode
17685 Head Pressure
18288 Speed of Sound
18289 Isentropic Head
18290 Omega
18242 Lead Surge Mach
18243 Lag Surge Mach
18305 Lead Anti-Surge Transient Offset
17778 Lag Anti-Surge Transient Offset
17680 Biased Anti-Surge Minimum Frequency
18240 Lead Surge Frequency
18241 Lag Surge Frequency
17681 Active Anti-Surge Minimum Frequency
17682 Lead Active Minimum PRV Position
17777 Evaporator Pressure Override Threshold
17776 Condenser Pressure Override Threshold
18251 Lead Motor Current Override Threshold