SECTION 2 – OPTIVIEW CONTROL CENTER
When the chiller system is powered on, the above de-
fault display appears. The primary values which must
be monitored and controlled are shown on this screen.
The Home Screen display depicts a visual representa-
tion of the chiller itself. Animation indicates chilled
liquid flow.
DISPLAY ONLY
Chilled Liquid Temperature - Leaving
Displays the temperature of the liquid as it leaves the
evaporator.
Chilled Liquid Temperature - Entering
Displays the temperature of the liquid as it enters the
evaporator.
Condenser Liquid Temperature - Leaving
Displays the temperature of the liquid as it leaves the
condenser.
Condenser Liquid Temperature - Entering
Displays the temperature of the liquid as it enters the
condenser.
Motor 1
Motor Run (LED)
On when the digital output controlling compressor #1
motor starter is on.
% Full Load Amps
Displays the percentage of compressor motor full load
amps being utilized by compressor #1 motor.
Input Power
Displays kW being utilized by compressor #1
motor. The input power display is not available on
units equipped with EM starters.
Operating Hours
Displays the total operating hours of compressor #1.
Motor 2
Motor Run (LED)
On when the digital output controlling compressor #2
motor starter is on.
% Full Load Amps
Displays the percentage of compressor motor full load
amps being utilized by compressor #2 motor.
Input Power
Displays kW being utilized by compressor #2
motor. The input power display is not available on
units equipped with EM starters.
Operating Hours
Displays the total operating hours of compressor #2.
HOME SCREEN
LD27843
FIGURE 4 - HOME SCREEN