EasyManua.ls Logo

York OPTIVIEW YD Series - Page 139

York OPTIVIEW YD Series
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
139
SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.79-O3
ISSUE DATE: 11/09/2018
2
“EVAPORATOR – TRANSDUCER OR TEMPER-
ATURE SENSOR”
A possible defective Evaporator pressure Transducer
or Refrigerant Temperature Sensor has been detected.
The Control Center converts the evaporator pressure to
a Saturated Temperature value and compares this val-
ue to the optional Evaporator Refrigerant Temperature
Sensor. If the difference between these temperatures
is greater than 3.0°F, continuously for 1 minute, this
shutdown is performed. This check is only performed
under the following conditions:
Chiller has been running for at least 10 minutes
Evaporator Refrigerant temperature (RT7) has
been enabled by a Service technician
Not in Brine cooling mode
Smart Freeze is enabled
Evaporator Temperature Sensor (RT7) or Evapo-
rator Saturation Temperature is indicating a tem-
perature of <32.0°F
The chiller can be started after the temperatures are
within 3.0°F of one another and the Operator presses
the Clear Faults button.
“DISCHARGE #1 – HIGH PRESSURE CON-
TACTS OPEN”
The contacts of the electro-mechanical high pressure
switch (HP1, located in the discharge line of compres-
sor #1) have opened because it detected a pressure
>180.0 psig. The contacts will automatically close
when the discharge pressure decreases to < 120.0 psig
and the Operator presses the Clear Faults button.
“DISCHARGE #2 – HIGH PRESSURE CON-
TACTS OPEN”
The contacts of the electro-mechanical high pressure
switch (HP2, located in the discharge line of compres-
sor #2) have opened because it detected a pressure
>180.0 psig. The contacts will automatically close
when the discharge pressure decreases to < 120.0 psig
and the Operator presses the Clear Faults button.
“DISCHARGE #1 – HIGH TEMPERATURE”
The chiller (both compressors) has shutdown because
the discharge temperature of compressor #1, as sensed
by thermistor RT2, has increased to >220.0 ºF. The
chiller can be started after the temperature decreases
to <220.0 ºF and the Operator presses the Clear Faults
button.
If compressor #1 is locked out using the Lockout key
on the Capacity Compressor Cycling Screen, this fault
does not cause compressor #2 to shutdown or prevent
it from starting. When this fault occurs on a locked-out
compressor, it is displayed as a warning. This allows
the user to know that a fault exists on the locked-out
compressor. The condition must be corrected prior to
the lockout being removed from the compressor. If it
is not, the warning condition will revert back to a shut-
down as soon as the lockout is removed and will cause
the chiller to trip.
“DISCHARGE #2 – HIGH TEMPERATURE”
The chiller (both compressors) has shutdown because
the discharge temperature of compressor #2, as sensed
by thermistor RT8, has increased to >220.0 ºF. The
chiller can be started after the temperature decreases
to <220.0 ºF and the Operator presses the Clear Faults
button.
If compressor #2 is locked out using the Lockout key
on the Capacity Compressor Cycling Screen, this fault
does not cause compressor #1 to shutdown or prevent
it from starting. When this fault occurs on a locked-out
compressor, it is displayed as a warning. This allows
the user to know that a fault exists on the locked-out
compressor. The condition must be corrected prior to
the lockout being removed from the compressor. If it
is not, the warning condition will revert back to a shut-
down as soon as the lockout is removed and will cause
the chiller to trip.
“DISCHARGE #1 – LOW TEMPERATURE”
The chiller (both compressors) has shutdown because
the discharge temperature of compressor #1, as sensed
by thermistor RT2, has decreased to <30.0 ºF. The
chiller can be started after the temperature increases
to >30.0ºF and the Operator presses the Clear Faults
button.

Table of Contents

Related product manuals