JOHNSON CONTROLS
101
SECTION 5 - COMMISSIONING
FORM 155.30-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
5
FORM 155.30-CL1.EN.UL
ISSUE DATE:12/11/2018
TABLE 3 - PURGE AMOUNT MEASUREMENT DATA SHEET (1/1)
User:
Model: YHAU - MFG.No.: User's machine code:
Measured Date: Measured by:
Purge Amount from Purge Line Flame Reaction Test
Standard: 4.0 cc/min. or smaller Reaction (Strong/Weak/None)
Amount of Gas (P) cc/min
Purge Amount from Purge Tank
Elapsed time 1 hour
Consumed time for measurement (m) min.
Total gas amount (a) cc
Actual gas amount (b) cc
(b) = (a) - (P) x (m)
Purge Amount from Absorber
Standard: 4.0 cc/min. or smaller
Elapsed time (T) min. 1 2 3 5 10 15 20 30
Total gas amount (A) cc
Increased gas amount (B) cc
Actual gas amount (C) cc/min.
(B) = (A) - previous(A)
(B) - (P) x { (T) - previous(T) }
(C) = (T) - previous(T)

Table of Contents