TABLE 2 - COMMISSIONING DATA SHEET (2/2) (HOT WATER SINGLE-EFFECT ABSORPTION CHILLER)
User:
Model: MFG.No.: User's machine code:
Running Data
Date: Measured by Specification Standard : : :
Hot Water
Hot water valve position % Control panel
Inlet temperature
°F
Control panel
Outlet temperature °F Control panel
Inlet pressure PSIG Pressure gauge
Outlet pressure
PSIG
Pressure gauge
[11] Pressure drop PSIG DPG or calculation [12]
[9] Flow rate
ft3/h
FM or calculation [10]
Chilled
Water
Inlet temperature
°F
Control panel
Outlet temperature
°F
Control panel
Inlet pressure PSIG Pressure gauge
Outlet pressure
PSIG
Pressure gauge
[3] Pressure drop
PSIG
DPM or calculation [4]
[1] Flow rate
ft3/h
FM or calculation [2]
Cooling
Water
Inlet temperature
°F
Control panel 68~89.6 °F
Outlet temperature
°F
Control panel
68~99.5°F
Inlet pressure PSIG Pressure gauge
Outlet pressure
PSIG
Pressure gauge
[7] Pressure drop
PSIG
DPG or calculation [8]
[5] Flow rate ft3/h FM or calculation [6]
Absorption
Cycle
Generator press. (Gauge)
PSIG
Compound gauge
Generator press. (Sensor)
mmHG.abs
Control panel
Generator temperature
°F
Control panel
<212°F
Generator conc. % Control panel
Absorber temperature
°F
Control panel
Refrigerant temperature °F Control panel
Liquid
Level
Generator – Level gauge
Absorber – Level gauge
Evaporator (Lower) – Level gauge
Evaporator (Upper) – Level gauge
NOTES:
Operating hours hours
Number of purge times times
Fill out each specication pressure drop according to the factory inspection report (actual value).
If differential pressure gauge (DPG) is not available, calculate each pressure drop.
If ow meter (FM) is not available, calculate each ow rate as below.
[1] = [2] x √[3]/[4] [5]=[6] x √[7]/[8] [9]=[10] x √[11]/[12]