SECTION 5 - COMMISSIONING
FORM 155.30-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
5
JOHNSON CONTROLS
6
FORM 155.30-CL1.EN.UL
ISSUE DATE:12/11/2018
TABLE 1 - COMMISSIONING DATA SHEET (1/2) (HOT WATER SINGLE-EFFECT ABSORPTION CHILLER)
User:
Model: MFG.No.: User's machine code:
Insulation Resistance Electric Power Supply
Standard: 5 MΩ or more (with 500 V meg-
ger)
R-Gnd S-Gnd T-Gnd
Specication: AC
V /
Hz
Circuit breaker MΩ Standard: Within +/- 10% of spec.
R-S V
U-Gnd V-Gnd W-Gnd R-T V
Solution circulation pump MΩ S-T V
Solution spray pump MΩ R-Gnd V
Refrigerant pump MΩ S-Gnd V
Purge pump MΩ T-Gnd V
Thermal Relay Setting Refrigerant Purity Temperature Setting
Solution circulation pump A Standard: 1.040 (kg/L) or less Cooling
Solution spray pump A Specic gravity Set. base temp.
°F
Refrigerant pump A Turbidity Auto. stop temp.
°F
Purge pump A Auto. restart diff.
°F
Pump Discharge Pressure Purge Amount
Solution circulation pump
PSIG
Standard: 4 cc/min or less
Solution spray pump
PSIG
Purge tank cc
Refrigerant pump
PSIG
Absorber cc