26 Unitary Products Group
XP036-060 Heating Capacities
115°F 125°F
1250
77 58.6 6.0 22.9 19.8 14.7 - - - 54.6 6.6 20.3 18.5 13.6 - - -
72 53.6 5.9 33.1 28.1 23.0 18.0 - - 49.4 6.5 31.3 26.4 21.5 16.6 - -
67 48.5 5.9 43.3 36.4 31.3 26.3 21.2 - 44.2 6.5 42.0 34.3 29.3 24.4 19.5 -
62 45.5 5.9 45.5 45.5 37.2 32.2 27.1 22.1 42.1 6.4 42.1 42.1 34.0 29.1 24.1 19.2
1500
77 60.0 6.0 27.9 22.1 16.3 - - - 55.7 6.6 26.5 20.8 15.1 - - -
72 54.8 6.0 37.1 31.2 25.4 19.6 - - 50.4 6.5 35.2 29.5 23.8 18.1 - -
67 49.7 5.9 46.2 40.4 34.5 28.7 22.9 - 45.1 6.5 43.9 38.2 32.5 26.8 21.0 -
62 46.5 5.9 46.5 46.5 41.0 35.2 29.4 23.5 43.0 6.5 43.0 43.0 37.6 31.9 26.2 20.5
57 46.6 5.9 46.6 46.6 41.1 35.3 29.5 23.6 43.3 6.4 43.3 43.3 37.9 32.2 26.5 20.7
1750
77 61.3 6.0 32.9 24.4 17.8 - - - 56.9 6.6 32.6 23.0 16.5 - - -
72 56.1 6.0 41.0 34.4 27.7 21.1 - - 51.5 6.6 39.0 32.5 26.0 19.5 - -
67 50.8 5.9 49.1 44.3 37.7 31.1 24.5 - 46.1 6.5 45.7 42.1 35.6 29.1 22.6 -
62 47.6 5.9 47.6 47.6 44.8 38.2 31.6 25.0 43.9 6.5 43.9 43.9 41.2 34.7 28.2 21.7
57 47.7 5.9 47.7 47.7 44.9 38.3 31.7 25.1 44.2 6.5 44.2 44.2 41.5 35.0 28.5 22.0
2000
77 62.7 6.0 37.9 26.7 19.3 - - - 58.1 6.6 38.7 25.2 18.0 - - -
72 57.3 6.0 44.9 37.5 30.1 22.7 - - 52.5 6.6 42.9 35.6 28.3 21.0 - -
67 51.9 5.9 51.9 48.3 40.9 33.5 26.1 - 47.0 6.5 47.0 46.0 38.7 31.4 24.1 -
62 48.6 5.9 48.6 48.6 48.6 41.2 33.8 26.4 44.8 6.5 44.8 44.8 44.8 37.6 30.3 23.0
57 48.7 5.9 48.7 48.7 48.7 41.3 33.9 26.5 45.1 6.5 45.1 45.1 45.1 37.9 30.6 23.3
2250
72 58.0 6.0 48.6 40.5 32.4 24.3 - - 53.3 6.6 47.0 38.9 30.9 22.8 - -
67 52.5 5.9 52.5 50.8 44.1 36.0 27.9 - 47.7 6.5 47.7 47.7 42.2 34.1 26.0 -
62 49.2 5.9 49.2 49.2 49.2 41.1 33.1 25.0 45.4 6.5 45.4 45.4 45.4 37.4 29.3 21.2
57 49.3 5.9 49.3 49.3 49.3 41.2 33.2 25.1 45.7 6.5 45.7 45.7 45.7 37.7 29.6 21.5
2500
72 58.7 6.0 52.3 43.5 34.8 26.0 - - 54.0 6.6 51.2 42.3 33.4 24.5 - -
67 53.2 5.9 53.2 53.2 47.3 38.5 29.8 - 48.3 6.5 48.3 48.3 45.6 36.8 27.9 -
62 49.8 5.9 49.8 49.8 49.8 41.1 32.3 23.6 46.0 6.5 46.0 46.0 46.0 37.2 28.3 19.4
57 49.9 5.9 49.9 49.9 49.9 41.2 32.4 23.7 46.3 6.5 46.3 46.3 46.3 37.4 28.6 19.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
XP060 (5.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
XP036-060
Size
(Tons)
Model
Air Over Evaporator
Coil
Capacity
1
&
kW
Outdoor Temperature (°F @ 72% RH)
CFM DB (°F) -10 0 10 20 30 40 50 60
036
(3.0)
XP
900
55
MBH 8.8 13.0 17.3 21.5 25.7 29.9 34.1 38.3
KW 1.61.61.71.71.81.91.92.0
70
MBH 5.5 9.8 14.0 18.2 22.4 26.6 30.8 35.0
KW 1.92.02.12.12.22.22.32.4
80
MBH 5.1 9.3 13.5 17.7 21.9 26.2 30.4 34.6
KW 2.22.22.32.42.42.52.62.6
1200
55
MBH 10.3 14.5 18.7 22.9 27.1 31.3 35.5 39.8
KW 1.21.31.41.41.51.61.61.7
70
MBH 7.0 11.2 15.4 19.6 23.8 28.0 32.2 36.4
KW 1.61.71.71.81.91.92.02.1
80
MBH 6.5 10.8 15.0 19.2 23.4 27.6 31.8 36.0
KW 1.81.92.02.02.12.22.22.3
1500
55
MBH 9.5 13.7 17.9 22.1 26.3 30.5 34.8 39.0
KW 0.50.60.70.70.80.90.91.0
70
MBH 6.2 10.4 14.6 18.8 23.0 27.3 31.5 35.7
KW 0.91.01.01.11.21.21.31.4
80
MBH 5.8 10.0 14.2 18.4 22.6 26.8 31.0 35.2
KW 1.21.21.31.41.41.51.51.6