Represented By:
Corporate Office:
2840 N. Lima Street
Burbank, CA 91504
Telephone: 818-565-1128
Fax: 818-565-1129
Website: www.steril-aire.com
Email: sales@steril-aire.com
Model No. Part No. Description Length Electrical Weight
Steril-Aire, Inc.
®
Model SEN Specifications
Ordering Information
T
h
e
U
V
C
E
m
i
t
t
e
r
T
M
and fixture shall be factory assembled and
tested. They shall consist of a housing, power source, Emitter socket
and Emitter.
T
h
e
h
o
u
s
i
n
g
shall be constructed of 304 stainless steel and shall be
powder coated to withstand the elements and HVAC environments.
Housing shall be equipped with a bottom side electrical opening to
facilitate wiring fixture to unit power. It shall incorporate all
components into one integral assembly that maximizes integrity and
serviceability. It shall be designed for mounting from outside the
airstream with only the Emitter in the conditioned air. Emitter shall
be held in place and supported in the airstream by a patented integral
collar, o-ring and heavy-duty spring wire fastener. The patented tube
mount section shall allow for quick and easy removal during lamp
replacement. The housing shall include an on-off switch.
T
h
e
p
o
w
e
r
s
o
u
r
c
e
shall be a Class P2, electronic rapid start type
with a power factor of >0.95 and a power conversion of >75%. It
shall be available in 115-208/230 and 277 Vac, 50/60 Hertz, and
single phase. It shall be designed to maximize photon production,
irradiance and reliability in cold or moving airstreams of 35-170° F,
100% RH and at up to 2000 fpm velocity. The design shall include
RF and EMI suppression.
T
h
e
s
o
c
k
e
t
shall be a Circline
®
4 pin type with sufficient wire length
to facilitate service.
T
h
e
E
m
i
t
t
e
r
shall be a very high output, hot cathode, T5 diameter,
Circline® cell-base type that produces a UVC band of 250-260 nm.
Each tube shall be capable of producing the specified output at up to
2000 fpm velocity and temperatures of 35-170° F. It shall produce no
ozone or other secondary contaminants.
I
n
d
e
p
e
n
d
e
n
t
t
e
s
t
i
n
g
:
The unit shall be tested by an independent test
laboratory in accordance with the general provisions of IES Lighting
Handbook, 1981 Applications Volume, and shall be verified through
independent testing to provide output per 1" arc length of not less
than 10 μW/cm2 at 1 meter in a 400 fpm airstream of 45° F.
Unit shall comply with UL Standard 1995 for use in HVAC
equipment and carry the "UL" and "ULC" labels.
SEN 1 VO 12001900 Single-Ended Fixture N/A 115, 208, 230V: 70-85 watts 3.3 lb.
SEN 1 VO 12002100 Single-Ended Fixture N/A 277V: 70-85 watts 3.3 lb.
GTS 16 VO 21000100 UVC Emitter 16" N/A 0.15 lb.
GTS 20 VO 21000200 UVC Emitter 20" N/A 0.15 lb.
GTS 24 VO 21000300 UVC Emitter 24" N/A 0.20 lb.
GTS 30 VO 21000400 UVC Emitter 30" N/A 0.20 lb.
GTS 36 VO 21000500 UVC Emitter 36" N/A 0.25 lb.
GTS 42 VO 21000600 UVC Emitter 42" N/A 0.25 lb.
© 2003 Steril-Aire 1109-07/05
Complies with current U.S. and Canadian UL Standards for
use in HVAC equipment.
This product may be covered by one or more of the following patents, others
pending: 5,334,347/ 5,866,076/ 5,817,276/ 6,372,186/ 6,313,470/ 6,245,293/
6,267,924/ 6,280,686/ 6,423,882.
http://www.rezine.ne