EasyManua.ls Logo

York ZJ Series - Blower Drive Selection Procedure; Drive Selection Example

York ZJ Series
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
251933-YTG-B-0806
Unitary Products Group 37
XP036-060 Bottom Duct Application
XP036 (3.0 Ton)-Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
0.2 0.3 0.4 0.5 0.6 0.7
RPM W BHP RPM W BHP RPM W BHP RPM W BHP RPM W BHP RPM W BHP
800 - - - 610 229 0.25 662 294 0.29 715 362 0.39 767 427 0.46 813 468 0.50
900 - - - 640 286 0.31 691 349 0.35 743 414 0.45 794 476 0.51 840 517 0.56
1000 620 287 0.31 669 344 0.37 719 404 0.41 770 466 0.50 833 564 0.61 879 605 0.65
1100 651 347 0.37 699 401 0.43 747 458 0.47 809 549 0.59 854 592 0.63
900 633 0.68
1200 681 407 0.44 728 458 0.49 786 538 0.54 830 581 0.62 875 623 0.67
920 664 0.71
1300 712 467 0.50 766 535 0.57 808 574 0.62 851 617 0.66
896 659 0.71 942 700 0.75
1400 749 541 0.58 789 576 0.62 830 616 0.66 874 658 0.71
918 701 0.75 964 742 0.80
1500 774 587 0.63 813 622 0.67 855 662 0.71
898 705 0.76 943 747 0.80 989 788 0.85
1600 801 639 0.69 840 674 0.72
881 714 0.77 925 757 0.81 970 799 0.86 1015 840 0.90
1700 830 697 0.75 869 732 0.79 911 772 0.83 954 814 0.87 999 857 0.92 1045 898 0.96
1800 862 760 0.81
901 795 0.85 943 835 0.90 986 877 0.94 1031 920 0.99 1077 960 1.03
1900
897 828 0.89 936 863 0.93 977 903 0.97 1021 945 1.01 1066 988 1.06 1111 1029 1.10
2000
934 901 0.97 973 936 1.00 1015 976 1.05 1058 1018 1.09 1103 1061 1.14 1149 1102 1.18
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1" filters. See STATIC RESISTANCE table for additional applications.
0.8 0.9 1.0 1.1 1.2 1.3
RPM W BHP RPM W BHP RPM W BHP RPM W BHP RPM W BHP RPM W BHP
800 860 505 0.54
916 561 0.60 966 595 0.64 1014 618 0.66 1060 635 0.68 1103 634 0.67
900
886 554 0.60 940 606 0.65 989 637 0.69 1036 657 0.70 1082 669 0.72 1124 663 0.70
1000
925 642 0.69 971 673 0.72 1017 696 0.75 1061 708 0.76 1103 708 0.76 1144 693 0.74
1100
946 670 0.72 992 701 0.75 1037 723 0.78 1082 736 0.79 1124 735 0.79 1165 721 0.77
1200 967 701 0.75 1013 732 0.79 1058 755 0.81 1102 767 0.82 1145 767 0.82 1185 752 0.81
1300
988 737 0.79 1034 768 0.82 1079 791 0.85 1123 803 0.86 1166 803 0.86
1400
1010 779 0.84 1056 809 0.87 1102 832 0.89 1146 844 0.91 1188 844 0.91
1500
1035 825 0.89 1081 856 0.92 1126 879 0.94 1170 891 0.96
1600
1062 877 0.94 1108 908 0.97 1153 931 1.00 1197 943 1.01
1700
1091 935 1.00 1137 966 1.04 1182 988 1.06
1800 1123 997 1.07 1169 1028 1.10
1900
1157 1066 1.14
2000
1195 1139 1.22
Factory Installed AK74 blower sheave and A39 belt.