York ZJ Series - Electric Heat Operation Errors; Electric Heat Safety Controls; Electric Heat Limit Switch Operation

York ZJ Series
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
251933-YTG-B-0806
46 Unitary Products Group
060
(5.0)
208-1-60 29.0 145.0 45.0 2.3 7.6 0.0
None - - 42.7 60
E05 4.0 19.2 66.7 80
E07 5.6 26.9 76.3 90
E10 8.0 38.5 90.7 100
E15 11.9 57.2 114.2 125
E20 15.9 76.4 138.2 150
E30 22.2 106.7 176.1 200
230-1-60 29.0 145.0 45.0 2.3 7.6 0.0
None - - 42.7 60
E05 5.3 22.1 70.3 90
E07 7.5 31.3 81.7 100
E10 10.6 44.2 97.9 110
E15 15.9 66.3 125.5 150
E20 21.2 88.3 153.1 175
E30 29.6 123.3 196.8 200
208-3-60 17.3 123.0 27.5 2.3 5.2 0.0
None - - 27.0 35
E05 4.0 11.1 40.9 50
E07 5.6 15.5 46.4 50
E10 8.0 22.2 54.8 60
E15 11.9 33.0 68.3 70
E20 15.9 44.1 82.2 90
E30 22.2 61.6 104.0 110
230-3-60 17.3 123.0 27.5 2.3 5.2 0.0
None - - 27.0 35
E05 5.3 12.7 42.9 50
E07 7.5 18.0 49.6 60
E10 10.6 25.5 58.9 60
E15 15.9 38.2 74.8 80
E20 21.2 51.0 90.7 100
E30 29.6 71.2 116.0 125
460-3-60 9.6 70.0 15.0 1.3 2.6 0.0
None - - 13.5 20
E07 6.8 8.2 23.7 25
E10 10.1 12.1 28.7 30
E15 13.6 16.4 34.0 35
E20 19.5 23.5 42.8 45
E30 28.8 34.6 56.8 60
575-3-60 7.5 53.0 11.7 1.3 2.0 0.0
None - - 10.3 15
E10 10.6 10.2 23.0 25
E15 15.9 15.3 29.4 30
E20 21.2 20.4 35.8 40
E30 30.4 29.3 46.9 50
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
XP036-060 (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Amps