25
Code Possible causes Action
1 Short circuit return sensor Check sensors, replace if needed
2 Interruption return sensor Check sensors, replace if needed
3 Short circuit supply sensor Check sensors, replace if needed
4 Interruption supply sensor Check sensors, replace if needed
5 Hardware error Exchange device
6
Battery empty or wrong temp.
sensor
Check device / sensor
7
Temperature out of measuring
range
Correction heating system,
check sensor type
100 Emergency operation Exchange device
1000 Battery life time exceed Exchange device
2000 Initial verication expired Exchange device
> 8000 Internal hardware error Exchange device
Error codes show faults detected by multidata WR3. If more than one error
appears, the sum of the error codes is displayed: Error 1005 = error 1000
and error 5.
Status display / Error codes
The symbols in the table below show the meter’s operational status. The
status messages only appear in the main display (energy). The tempo-
rary display of the warning triangle can be caused by special operating
states and does not always mean that the device is malfunctioning.
However, should the symbol be displayed over a longer period of time,
you should contact the service company! The corresponding error codes
can be found in the third menu level.
Symbol Status Action
External voltage -
Flow existent -
Attention! Check system /device for errors
■
Symbol ashing:
Data transmission
■
Symbol constantly displayer:
optical interface active
-
-
Emergency operation Exchange device