EasyManua.ls Logo

Zte ZXMW NR8250 - 134237782 SNCP Route Setting Alarm; 9001 AC Input Switch off

Zte ZXMW NR8250
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter2Alarm
lIfyes,disabletheloopbackfunctionafterthetestormaintenanceiscompleted.
(Path:Maintenance>RadioPort).
lIfno,gotostep2.
2.ReplacetheRMUboard.
2.1.24134237782SNCProutesettingalarm
AlarmProperty
lAlarmCode:134237782
lAlarmInformation:ThealarmisreportediftheSNCProutesettingfails.
lAlarmLevel:Major
lAlarmType:EquipmentAlarm
Sub-codeDescription
None.
EffectontheSystem
Theservicesusingthisrouteareinterrupted.
PossibleCauses
ThesystemfailstoconguretheSNCProute.
HandlingProcedure
Invalidatetherouteagain.
2.1.259001ACinputSwitchOff
AlarmProperty
lAlarmCode:9001
lAlarmInformation:ACinputswitchisoff
lAlarmLevel:Critical
lAlarmType:EquipmentAlarm
Sub-codeDescription
None
EffectontheSystem
1.Therectierfailstoworknormally,onlythebatterycanwork.
2.Whenthebatteryrunsout,thebasestationispowereddown.
2-19
SJ-20111008094748-008|2012–05–30(R1.1)ZTEProprietaryandCondential