EasyManua.ls Logo

Zte ZXMW NR8250 - DC Input Voltage Abnormal; 4011 Outdoor Access-Control Alarm

Zte ZXMW NR8250
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ZXMWNR8250AlarmandNoticationHandlingReference
HandlingProcedure
None
2.4.6401DCinputvoltageabnormal
AlarmProperty
lAlarmCode:401
lAlarmInformation:ThisalarmisreportedwhentheDCinputvoltageisoutofrange
andclearedwhenthevoltagebecomesnormal.
lAlarmLevel:Major
lAlarmType:EnvironmentAlarm
Sub-codeDescription
lSub-code0:Overvoltage
lSub-code1:Undervoltage
EffectontheSystem
Theboardorthesystemcannotoperateproperly,andtheservicescarriedbytheboard
areinterrupted.
PossibleCauses
lWhentheinputvoltageofPMboardishigherthantheupperthreshold,itis
over-voltage.
lWhentheinputvoltageofPMboardislowerthanthelowerthreshold,itis
under-voltage.
HandlingProcedure
Over-voltage:UseamultimeterorothertoolstocheckwhethertheinputDCvoltageis
higherthanorequalto56V.Ifyes,replacetheDCpowersupplysystem.Ifnot,replace
thePMboard.
Under-voltage:UseamultimeterorothertoolstocheckwhethertheinputDCvoltageis
lowerthan42V.Ifyes,replacetheDCpowersupplysystem.Ifnot,replacethePMboard.
2.4.74011Outdooraccess-controlalarm