LCD DISPLAY SCREENS
MODGAS-XWR2 Technical Guide
28
Conguration Screens
TEMP SCL
FAHRENHT or
CELSIUS
TEMPERATURE SCALE
Fahrenheit (default) or Celsius (Used in stand-alone mode only).
VLV STRT
POS
55-100%
VALVE START POSITION
Range is 55-100% in 5% steps. Default is 70%.
STG UP
DLY 1 TO 10 m
STAGE UP DELAY
Range is 1 to 10 minutes. Default is 3.
IGN RTRY
DLY 1-60 m
IGNITION RETRY DELAY
Range is 1-60 minutes. Default is 30.
STG DOWN
DLY 1 TO 10 m
STAGE DOWN DELAY
Range is 1 or 10 minutes. Default is 1.
LOSAT SU
0-45°F
LOW SUPPLY AIR TEMPERATURE START-UP
Range is 0 - 45ºF. Default is 40ºF.
If the Supply Air Temperature is 40° (adjustable) or less,
the stage up delay is reduced from 3 minutes to 1 minute.