EasyManuals Logo
Home>AAON>Control Unit>RSMVQ

AAON RSMVQ User Manual

AAON RSMVQ
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
11RSMVQ Technical Guide
INPUTS AND OUTPUTS
RSMVQ Inputs and Outputs
RSMVQ Inputs and Outputs
+5 - VDC Power
This output is a 5 VDC output that supplies power to the Head
Pressure Transducer 1.
HP1 - Head Pressure Transducer 1
The Head Pressure Transducer is used to measure Head Pressure
at the discharge line. This Head Pressure is used to drive
Condenser Fan 1 to maintain a given Head Pressure Setpoint.
+5 - VDC Power
This output is a 5 VDC output that supplies power to the Head
Pressure Transducer 2.
HP2 - Head Pressure Transducer 2
The Head Pressure Transducer is used to measure Head Pressure
at the discharge line. This Head Pressure is used to drive
Condenser Fan 2 to maintain a given Head Pressure Setpoint.
TEMP1 - Discharge Temperature Sensor 1
This sensor is the Discharge Line Temperature Sensor for Circuit 1.
It is the G010470 Thermistor 10K ohm strap-on pipe sensor.
It is strapped to the discharge line immediately after the VFD
compressor and is used as a safety against high compressor
temperatures. Units with Copeland VFDs have the Discharge
Line Temperature Sensor wired directly to the drive. Units with
Danfoss VFDs will have a Discharge Line Temperature Sensor
wired to TEMP 1 of the RSMVQ.
TEMP2 - Saturation Temperature Sensor 2
This sensor is the Suction Saturation Temperature Sensor for
Circuit 2. It is the G049490 Thermistor 10K strap-on pipe
sensor. It is strapped to the evaporator coil immediately after
the Thermal Expansion Valve (TXV) and is used to measure the
Suction Saturation Temperature of the second circuit.
BI1 - Compressor Status 1
A wet contact closure (24 VAC) on this input indicates
Compressor 1 is running. Typically, the source for this is a relay
output from the VCCX2. If BI1 opens, a compressor alarm will
be generated. Compressor 1 relay needs to be congured on the
VCCX2 as “A1 Compressor Run Status.
BI2 - Compressor Status 2
A wet contact closure (24 VAC) on this input indicates
Compressor 2 is running. Typically, the source for this is a relay
output from the auxiliary contact on the compressor starter. If
BI2 opens, Compressor 2 Enable relay and Compressor 2 High
Speed Enable relay will de-energize and a compressor alarm
will be generated.
NOTE: The binary inputs require wet contacts (24 VAC
only) to recognize an active input. If you provide
dry contacts, the contact closure will not be
recognized.
AO1 - Condenser Fan 1 VFD Signal
This is a direct acting output signal that is used to modulate the
Condenser Fan 1 VFD (0-10 VDC signal) on an air cooled unit.
AO2 - Condenser Fan 2 VFD Signal
This is a direct acting output signal that is used to modulate the
Condenser Fan 2 VFD (0-10 VDC signal) on an air cooled unit.
EXV-1 - Electronic Expansion Valve
The EXV-1 is the communications port for EXV setpoints and
status communications.
EXV-2 - Electronic Expansion Valve
The EXV-2 is the communications port for EXV setpoints and
status communications.
RLY1 - Compressor 2 Enable
This relay turns on Compressor 2.
RLY2 - Compressor 2 High Speed Enable
This relay enables high speed on Compressor 2.
RLY3 - Condenser 1 Enable
This relay enables Condenser Fan 1.
RLY4 - Condenser 2 Enable
This relay enables Condenser Fan 2.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AAON RSMVQ and is the answer not in the manual?

AAON RSMVQ Specifications

General IconGeneral
BrandAAON
ModelRSMVQ
CategoryControl Unit
LanguageEnglish

Related product manuals