9RSMVQ Technical Guide
WIRING
RSMVQ Outputs Wiring
Figure 3: RSMVQ Outputs Wiring
18-30 VACGND
Line
Voltage
NOTE:
All relay outputs are normally open
and rated for 24 VAC power only,
1 amp maximum load.
COMPRESSOR 2 HI SPEED
COMPRESSOR 2 ENABLE
24 VAC ONLY
CONDENSER 1 ENABLE
Connect to
VCCX2
Controller
1
Copeland VFD
Drive Board
2
3
4
56
R+ to PIN 1
T- to PIN 4
SH to PIN 5
Superheat Controller’s
E-BUS Terminal
Superheat Controller’s
E-BUS Terminal
CONDENSER 2 ENABLE
Copeland
Packaged VFD
Danfoss VFD
T- to Term 69
SH to
Term 61
4
5
61 2 3
7
8
RS-485
Interface
69
68
61
Ground shield
wire on one end
4
5
61 2 3
7
8
4
5
61 2 3
7
8
R+ to Term 68
RED
GRN
BLK
RED
GRN
BLK
R+ to PIN 2
T- to PIN 7
SH to PIN 3
Ground shield
wire on one end
AAON P/N: ASM02293
+24 VAC
GND
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
CONDENSER 1
COMP 2 ENABLE
COMP 2 HI SPEED
ANALOG OUTPUTS
COMMON
RELAY OUTPUTS
LABEL P/N:
G079120
COND FAN 1
COND FAN 2
GND
24 VAC POWER ONLY
WARNING! POLARITY
MUST BE OBSERVED
OR THE CONTROLLER
WILL BE DAMAGED
CONDENSER 2
+5 V
DISCHARGE TEMP 1
COMP STAT 1
H1P
SATURATION TEMP 2
COMP STAT 2
GND
NOT USED
GND
NOT USED
GND
BINARYINPUTS
MODBUS
RSMVQ
www.aaon.com
HEAD
PRESSURE
SENSORS
DUAL
E-BUS
EXP VALV E1
+5 V
H2P
GND
NOT USED
NOT USED
GND
NOT USED
EXP VALV E2
R+
T-
SH
SHD
T-
R+
SHD
T-
R+
EXP VALV E3
NOT
INSTALLED
EXP VALV E4
NOT
INSTALLED
EACH EXP VALVE IS INDIVIDUALLY
ELECTRICALLY ISOLATED
NOT USED
ALARM
UP
DOWN
ENTERMENU