44
High Discharge Pressure Alarm
The high discharge pressure alarm will
enable if the high pressure switch opens.
This alarm will disable the compressor but
allow the supply fan to operate.
Low Suction Pressure Alarm
The low suction pressure alarm will activate
and turn the compressor off if the low
suction pressure switch is open for 10
seconds. The alarm will deactivate if 15
minutes has expired and the low pressure
switch has closed. If the alarm is activated
again within two hours, the unit power must
be cycled off and on.