1. Mount the angle frame into the panel cut-out with four M4 screws.
C
A
B
D
E
F
G
H
A070586 V2 EN
Figure 10: Mounting the angled frame
A 6.97 inches (177 ±0.3 mm)
B 6.57 inches (167 ±1 mm)
C 7.99 inches (203 ±1 mm)
D 1.59 inches (40.5 mm)
E 4.80 inches (122 ±0.3 mm)
F 1.59 inches (40.5 mm)
G 0.22 inches (5.5 mm)
H 7.48 inches (190 mm)
2. Loosen the four M5 fixing screws in the case to fit the case into the angle frame.
3.
Mount the case to the angle frame.
With the angled frame, the IED can be mounted inclined downward to a 25° angle.
4. Tighten the screws.
The allowed range for the fixing screws’ tightening torque is 0.52...0.74 foot-
pounds (0.7...1 Nm).
5. Install the plug-in unit into the case.
1MAC051065-MB C Section 4
Mounting
615 series ANSI 23
Installation Manual