Section 5 Connecting
5.1
Required tools
Only use a screwdriver and insert bits for Phillips (PH 1) cross-recessed head screws
when handling CT/VT terminals (X2.1) of screw-compression type.
5.2 Connecting wires
All connections are made on the rear of the case. No soldering is needed.
See the application manual for product-specific connection diagrams.
Connect each signal connector (X100 and X110) terminal with one 14 or 16
Gauge wire. Use 12 or 14 Gauge wire for CB trip circuit.
Connect each ring-lug terminal for signal connector X120 with one of maximum
14 or 16 Gauge wire.
Connect each ring-lug terminal for CTs/VTs with one 12 Gauge wire.
5.2.1 Connecting ring-lug type wires
Ring-lug type insulated terminal should be used for signal connector X120. Use a
number 2 Philips screw driver for Ring lug terminals.
5.3 Connecting protective grounding
The ground lead must be at least a 10 Gauge wire. If the length of the
earth lead is long, the cross section of the wire must be increased.
1MAC051065-MB C Section 5
Connecting
615 series ANSI 33
Installation Manual