104 ACS 400 User’s Manual
Group 34: Process Variables
Parameters of this group can be used to create custom process variables. Values of process
variables can be seen in parameters 0134
PROCESS VAR 1 and 0135 PROCESS VAR 2 AND optionally
in the ACS-PAN output display. Value is calculated by taking given parameter from the operating
data group (Group 1), and multiplying and dividing it with given coefficients. The unit and number of
decimal digits is configurable.
See example below.
Code Description
3401 DISPLAY SEL
Selects displayed variables for the output display of
the ACS-PAN control panel.
1 =
STANDARD
Panel displays standard variables.
2 =
PROCESS VAR
Panel displays process variables. See Figure 42.
Figure 42 ACS-PAN output display when
process variable display is selected.
3402 P VAR 1 SEL
Selection of process variable 1. Number of any parameter of the group 1
OPERATING DATA.
3403 P VAR 1 MULTIP
Process variable 1 multiplier.
3404 P VAR 1 DIVISOR
Process variable 1 divider.
3405 P VAR 1 SCALING
Decimal point location of process variable 1, when
displayed. Refer to Figure 43.
Figure 43 Display with different decimal point
locations when calculated value is 125.
3406 P VAR 1 UNIT
Process variable unit.
0.0A 50.0 Hz
0.0 Hz
OUTPUT
Process variable 1 Frequency reference
Process variable 2
Value Display
0125
112.5
21.25
30.125
0 = NOT SEL 4 = % 8 = kh 12 = mV 16 = °F 20 = m
3
/h 24 = GPM 28 = MGD
1 = A 5 = s 9 = °C 13 = kW 17 = hp 21 = dm
3
/s 25 = PSI 29 = inHg
2 = V 6 = h 10 = lb ft 14 = W 18 = MWh 22 = bar 26 = CFM 30 = FPM
3 = Hz 7 = rpm 11 = mA 15 = kWh 19 = m/s 23 = kPa 27 = ft 31 = Cst