ACS 400 User’s Manual 57
Application Macro 3-wire
This macro is intended for those applications where the drive is controlled using momentary push-
buttons. It gives two more preset speeds compared to Factory Macro (1) by using DI4 and DI5.
The value of parameter 9902 is 2 (3-
WIRE).
*Constant speed selection: 0 = open, 1 = connected
Note! Stop input (DI2) deactivated: panel START/STOP button interlocked (local).
Application Macro 3-wire parameter values:
Input signals Output signals Jumper Setting
• Start, stop and direction
(DI1,2,3)
• An. output AO: Frequency
• Analog reference (AI1) • Relay output 1: Fault
• Preset speed selection (DI4,5) • Relay output 2: Running
DI4 DI5 Output
00Reference through AI1
10Constant speed 1 (1202)
01Constant speed 2 (1203)
11Constant speed 3 (1204)
1001
EXT 1 COMMANDS 4 (DI1P,2P,3) 1402 RELAY OUTPUT 22 (RUN)
1002
EXT 2 COMMANDS 0 (NOT SEL) 1503 AO CONTENT MAX 60 Hz
1003
DIRECTION 3 (REQUEST) 1601 RUN ENABLE 0 (NOT SEL)
1102
EXT1/EXT2 SEL 6 (EXT1) 1604 FAULT RESET SEL 0 (KEYPAD)
1103
EXT REF1 SELECT 1 (AI1) 2008 MAXIMUM FREQ 60 Hz
1105
EXT REF1 MAX 60 Hz 2105 PREMAGN SEL 0 (NOT SEL)
1106
EXT REF2 SELECT 0 (KEYPAD) 2201 ACC/DEC 1/2 SEL 0 (NOT SEL)
1201
CONST SPEED SEL 8 (DI4,5) 4001 PID GAIN 1.0
1401
RELAY OUTPUT 13 (FAULT (-1)) 4002 PID INTEG TIME 60 s
External Reference 1: 0...10 V <=> 0...50 Hz
Reference voltage 10 VDC
Not used
Output frequency 0...20 mA <=> 0...50 Hz
+24 VDC
Momentary activation with DI2 activated: Start
Momentary deactivation: Stop
Activate to reverse rotation: Fwd/Rev
Constant speed selection*
Constant speed selection*
Relay output 1, programmable
Default operation: fault => 17 connected to 18
Relay output 2, programmable
Default operation: running => 20 connected to 22