EasyManua.ls Logo

ABB ACS 400 - Page 135

ABB ACS 400
187 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
124 ACS 400 Users Manual
3 = DI3
Interlocks function is in use. Depending on the number of motors, the digital inputs are reserved for the
interlock signals according to the following table.
4 = DI4
Interlocks function is in use. Depending on the number of motors, the digital inputs are reserved for the
interlock signals according to the following table.
Code Description
Interlock signals
No of aux. motors
(param. 8117)
ACS 400 digital
inputs
NDIO module 1 NDIO module 2
0 DI1-DI2: free
DI3: Motor 1
DI4-DI5 free
Not used Not used
1 DI1-DI2: free
DI3: Motor 1
DI4: Motor 2
DI5: free
2 DI1-DI2: free
DI3: Motor 1
DI4: Motor 2
DI5: Motor 3
3 DI1-DI2: free
DI3: Motor 1
DI4: Motor 2
DI5: Motor 3
DI1: Motor 4
DI2: Unused
Not used
Interlock signals
No of aux. motors
(param. 8117)
ACS 400 digital
inputs
NDIO module 1 NDIO module 2
0 DI1-DI3: free
DI4: Motor 1
DI5 free
Not used Not used
1 DI1-DI3: free
DI4: Motor 1
DI5: Motor 2
2 DI1-DI3: free
DI4: Motor 1
DI5: Motor 2
DI1: Motor 3
DI2: unused
3 DI1-DI3: free
DI4: Motor 1
DI5: Motor 2
DI1: Motor 3
DI2: Motor 4
Not used