136 ACS 400 User’s Manual
Table 17 Analog output control.
Group 14
RELAY OUTPUTS
1401
RELAY OUTPUT 10 = NOT SEL
...
7 =
SUPRV1 OVER
8 = SUPRV1 UNDER
9 = SUPRV2 OVER
10 = SUPRV2 UNDER
...
31 =
STARTED
e.g. 7 (SUPERV1
OVER)
Relay output 1 function.
With the given setting, the relay 1 is
activated when supervised parameter 1
(given by parameter 3201) is above the
limit given by parameter 3203.
1402
RELAY OUTPUT 2 As above e.g. 7 (SUPERV1
OVER)
Relay output 2 function.
See above.
Group 32
SUPERVISION
3201
SUPERV 1 PARAM 102 - 137 e.g. 131 (SERIAL
LINK DATA 1)
Number of supervised parameter 1. Any
parameter of the group 1 OPERATING
DATA.
3202
SUPERV 1 LIM LO 0 - 255 e.g. 100 Lower supervision limit for supervised
parameter 1.
3203
SUPERV 1 LIM HI 0 - 255 e.g. 100 Upper supervision limit for supervised
parameter 1.
3204
SUPERV 2 PARAM 102 - 137 e.g. 132 (SERIAL
LINK DATA 2)
Number of supervised parameter 1. Any
parameter of the group 1 OPERATING
DATA.
3205
SUPERV 2 LIM LO 0 - 255 e.g. 100 Lower supervision limit for supervised
parameter 2.
3206
SUPERV 2 LIM HI 0 - 255 e.g. 100 Upper supervision limit for supervised
parameter 2.
Code Parameter Name
Alternative
Settings
Setting for
Standard
Modbus
Function/Information
Group 01
OPERATING DATA
0133
SER LINK DATA 3 0 - 255 - Controlling data for the analog output.
Group 15
ANALOG OUTPUT
1501
AO CONTENT 102 - 137 e.g. 133 Directs the contents of parameter 133 to
the analog output.
1503
AO CONTENT MAX 255 Analog output scaling: upper limit (20 mA)
reached when value 255 is written to
parameter 133.
Code Parameter Name
Alternative
Settings
Setting for
Standard
Modbus
Function/Information