EasyManua.ls Logo

ABB ACS2000 AFE 1MVA - Page 123

ABB ACS2000 AFE 1MVA
177 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
123 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV. J
For further information on the CDP control panel,
see Chapter 9 - CDP control panel.
8.4.1 Lamp test
The lamp test is activated via the CDP control panel
by setting parameter 16.7 to LAMP TEST. The lamp-
test function resets itself after a set time.
References
8-1 Local operator panel
8-1
1. CDP control panel
Main functions:
- Starts and stops the motor
-Displays status messages
- Displays alarm and fault messages of the drive and moni-
tored foreign equipment
- Resets alarm and fault messages
-
2. Supply ON
Illuminated pushbutton. When pressed, it lights up and turns
the main power supply on (the main circuit breaker closes
and the DC link charges).
3. Supply OFF
Illuminated pushbutton. When pressed, it lights up and turns
the main power supply off (the main circuit breaker opens
and the DC link discharges).
4. Alarm / Fault lamp
- Fault: permanent light
- Alarm: flashing light
5. Grounding Switch Unlocked
Illuminated pushbutton. It lights up if the grounding-switch
can be released by pushing the Grounding Switch Unlocked
pushbutton.
Keep this pushbutton pressed to turn the grounding switch
to the grounded or ungrounded position.
Note: This pushbutton also works as a test lamp. To test its
functionality, press it and verify that it lights up.
6. Emergency Reset pushbutton (option)
Resets the emergency-off relay of the drive control system
Flashes when the auxiliary voltage is switched on, or when an
emergency-off switch is pressed
7. Emergency Off
Latching pushbutton. When pressed during operation of the
drive, the main circuit breaker opens immediately and the DC
link discharges. When pressed at standstill of the drive, it
prevents the drive from starting.
1
3
2
4
5
6
7

Related product manuals