Adding drives to PROFINET
After installing GSDML file, a new drive PROFINET modules appear in the hardware library.
1. Drag and drop FENA-11 according to your actual fieldbus module type to the PROFINET.
Figure 17 FENA-11
2. Double-click FENA drive to set the IP address.
3. In the Properties window, add Device name (FENA) and click Ethernet to set the PROFINET IP
address for the fieldbus module. Click OK.