Actual signals and parameters 63
9905 MOTOR NOM
VOLT
Defines the motor nominal voltage.
• For AM, nominal voltage is the value displayed on
the motor name plate.
• For PMSM, nominal voltage is back emf voltage at
nominal speed.
The inverter cannot supply the motor with a voltage
greater than the input voltage.
Note: The output voltage is not limited by the nominal
motor voltage, but increases linearly up to the value of
the input voltage.
Motor nominal voltage plot
Warning! The stress on the motor insulations
depends on the inverter supply voltage. This
also applies when the motor voltage rating is
lower than the inverter rating and the supply voltage of
the inverter.
The rms voltage can be limited to the motor nominal
voltage by setting the maximum frequency of the
inverter in parameter 2008 to the motor nominal
frequency.
1 = 1 V
0.5...1.5 * U
1N
Incoming AC voltage as displayed on the inverter
name plate.
200 V units:
46...345 V
400 V E
units:
80...600 V
9906 MOTOR NOM
CURR
Defines the nominal motor current as displayed on the
motor rating plate.
l
2N
0.2...2.0 l
2N
Rated current as displayed on the inverter name plate. 1 = 0.1 A
All parameters
No. Name/
Value
Description Def/ FbEq
Input voltage
Output
frequency
Output
oltage
9905
9907