64 Actual signals and parameters
9907 MOTOR NOM
FREQ
Defines the nominal motor frequency at which the
output voltage equals the motor nominal voltage:
50 Hz
10.0...600.0 Hz Nominal motor frequency 1 = 0.1 Hz
9908 MOTOR NOM
SPEED
Defines the nominal motor speed as displayed on the
motor rating plate.
Type
Dependent
50...30000 rpm Nominal motor speed 1 = 1 rpm
9909 MOTOR NOM
POWER
Defines the nominal motor power as displayed on the
motor rating plate.
P
N
0.2...3.0* P
N
kW Rated power as displayed on the inverter name plate. 1 = 0.1 kW/
0.1 hp
9910 ID RUN Controls self -calibration process called Motor ID run.
During this process, the inverter operates the motor
and makes measurements to identify motor
characteristics and create a model used for internal
calculations.
OFF/
IDMAGN
OFF/IDMAGN The motor ID run process is not run. Identification
magnetization is performed depending on the motor
control mode. See 9904 MOTOR CTRL MODE, page
62. In identification magnetization, the motor model is
calculated at first start by magnetizing the motor for 10
to 15 seconds at zero speed (motor not rotating,
except that a permanent magnet synchronous motor
can rotate a fraction of a revolution). The model is
recalculated always at start after motor parameter
changes.
Parameter 9904 = 1 (VECTOR: SPEED):
Identification magnetization is performed.
Parameter 9904 = 3 (SCALAR: FREQ):
Identification magnetization is not performed.
Note: The parameter 9904 = 2 (VECTOR: TORQ) is
not functional in the ACS355 solar pump inverter.
0
All parameters
No. Name/
Value
Description Def/ FbEq
FieldWeakeningPoint
NominalFrequency SupplyVoltage×
MotorNominalVoltage
-----------------------------------------------------------------------------------------------------------
=