Option 113
• Set parameters for inductor bypass contactor.
If inductor bypass contactor is used as a c-plus option, below parameters need to be
set. Inductor bypass contactor can only be used when MB and MSS are steady signal
control (one coil control).
85.20 MB open by
direct online
Disabled
(example)
If it’s enabled, 1 →0 of MB DOL command (BCU DI4, or 85.01 SBU
control and monitoring CW bit 2) will open MB. For Multi motor,
disabled is necessary.
97.40 Output choke
inductance
1.48mH
(example)
Define the inductance of the output choke.
97.46 SBU current
control gain
0.25
(example)
Gain for current close loop control. The value needs to be confirmed
during commissioning.
Drive Parameter setting Description