114 Option
Set MAU PLC parameters.
If more than one motors are to be sync to mains, marshalling PLC (optional) is used.
It
provides parameters, events and IO signals interface to user. Web visualization is used as
interface of marshalling PLC.
Requirements for commissioning PC
1. In order to access PLC, user’s computer has to meet below conditions.
Operating system: Windows NT/2000/XP/7/10, Windows CE, Linux, RTE.
A Web-Browser (IE-Explorer or Netscape)
JavaScript is installed on PC. The Java.exe installation could be downloaded from the
official website https://www.java.com/en/
2. IP address and Subnet mask setting
Connect Marshalling PLC and PC with ethernet cable.
Set Marshalling PLC (optional) and Panel (optional) as below table.
set the PC IP address in the same segment, e.g. 192.168.0.13, and with same Subnet
mask.
Drive parameter Setting Description
16.19 DIO3 function Output Select DIO3 as output
16.21 DIO3 output
source
P 85.2.14 Inductor bypass contactor close command signal is from
SBU function SW bit 14
16.24 DIO4 function Output Select the DIO4 as the output
16.26 DIO4 output
source
P 85.2.15 Inductor bypass contactor open command signal is from
SBU function SW bit 15
85.21 Bypass
contactor control
Enabled Enable inductor bypass contactor control
85.22 Contactor
control signal
Pulse signal Inductor bypass contact is using pulse signal for control
Marshalling PLC Panel (CP610)
IP address 192.168.0.10 192.168.0.11
Subnet mask 255.255.255.0 255.255.255.0