116 Option
• Connect the Marshalling PLC and PC with Ethernet cable.
• Open http://192.168.0.10/webvisu.htm by Internet Explorer to show Web visualization.
• Input service level pass code in Par.24.
Marshalling PLC
parameter
Setting Description
Par.10 MSS close
time limit
3s
(example)
Define maximum operating time for closing MSS
Par.11 MB open
time limit
3s
(example)
Define maximum operating time for opening MB
Par.12 MSS open
time limit
3s
(example)
Define maximum operating time for opening MSS
Par.13 MSS close
waiting time
5s
(example)
Define the MSS operating waiting time, after switching off the motor.
Par.14 Motor grid
configure
External
(example)
Two grids are supported. This parameter defines the grid selection
command source. External means it’s from DI (X106: 1, 2).
Parameter means it’s from Motor1 grid selection... Motor8 grid
selection.
Par.23 PLC IO
refresh
Done
(example)
In case PLC reports F002 PLC IO configuration fault,
refresh PLC configuration to match actual IO modules.
After refreshing, PLC will reboot and configure correct
hardware.
This parameter will be displayed only if PLC has IO
configuration fault.
Par.50 Motor 1
user set
UserSet1
(example)
This parameter selects the user set for this motor.
Two types of motors are supported and user set is used to select the
corresponding motor data. The command is from marshalling PLC to
BCU DI5, to select user set. Every time after Motor group 1...8
selection is set, marshalling PLC will select corresponding use set.
Detailed steps:
1. Using motor data 1 for commissioning.
2. Set 96.11 User set save/load to Save to set 1. After saving is
finished, it will change to No action.
3. Set motor data 2 (99.06...99.11).
4. Set 96.11 User set save/load to Save to set 2. After saving is
finished, it will change to No action.
5. Set 96.12 User set I/O mode in1 to DI5, 96.11 User set
save/load to User set I/O mode. 96.10 User set status will show
the user set selected by marshalling PLC.
Par.51 Motor 1
grid selection
External
(example)
This parameter selects the grid for this motor. It works only when Par.
14 Motor grid configure is Parameter.
Par.52 MB1 open
DOL enable
Disable
(example)
Parameter selects if MB1 open command is set if the direct online
(DOL) signal is removed (1→0).
Par.53 MB1 close
DOL enable
Disable
(example)
Parameter selects if MB1 close command is set if the direct online
(DOL) signal is set (0 →1).
Set for motor 2 to
motor 8
if SBM>=0002