Option 133
3. General configuration of speed follower
20.6 Ext2 commands M/F link
20.7 Ext2 start trigger type level
26.12 Torque ref2 source M/F reference 2
60.1 M/F comm port RDCO CH2 Channel of DDCS M/F
60.2 M/F node address 2 to 60 ID of this Follower
60.3 M/F mode DDCS follower
60.9 M/F comm loss
function
Fault Follower’s action when comm loss happens
60.11 M/F ref2 type Torque
62.1 M/F data 1 selection CW 16bit Follower selects the data which receive from
the master. The data value shown as
P62.25~27
62.2 M/F data 2 selection Ref1 16bit
62.3 M/F data 3 selection Ref2 16bit
61.1 M/F data 1 selection SW 16bit (Optional) Follower select the data which
transmit to the master, and they are effective
when this follower is selected by Master’s
P60.14
61.2 M/F data 2 selection User dependent
61.3 M/F data 3 selection User dependent
ACS580MV Follower Parameter Settings Speed Follower
Parameter Name Setting Description
19.11 Ext1/Ext2 selection Ext2
19.14 Ext2 control mode Speed
20.6 Ext2 commands M/F link
20.7 Ext2 start trigger type level
22.12 Speed ref2 source M/F reference 1
60.1 M/F comm port RDCO CH2 Channel of DDCS M/F
60.2 M/F node address 2 to 60 ID of this Follower
60.3 M/F mode DDCS follower
60.9 M/F comm loss function Fault Follower’s action when comm loss
happens
60.10 M/F ref1 type Speed
62.1 M/F data 1 selection CW 16bit Follower select the data which receive
from the master. The data value
shown as P62.25~27
62.2 M/F data 2 selection Ref1 16bit
62.3 M/F data 3 selection Ref2 16bit
ACS580MV Follower Parameter Settings — Torque Follower