Loading...
Technical data
98
gG fuses
* maximum total I
2
t value for 550 V or 690 V
1)
minimum short-circuit current of the installation
Note 1: See also Planning the electrical installation: Thermal overload and short-circuit protection. For
UL recognized fuses, see NEMA data on page 103.
Note 2: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses than the recommended ones must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of
the fuse does not exceed the melting curve of the fuse mentioned in the table.
ACS800-04 size Input
current
Min. short-
circuit
current
1)
Fuse
AAA
2
s * V Manufacturer Type IEC size
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0025-2 67 1050 80 34500 500 ABB Control OFAF000H80 000
-0030-2 81 1480 100 63600 500 ABB Control OFAF000H100 000
-0040-2 101 1940 125 103000 500 ABB Control OFAF00H125 00
-0050-2 138 2400 160 200000 500 ABB Control OFAF00H160 00
-0060-2 163 2850 200 350000 500 ABB Control OFAF1H200 1
-0070-2 202 3300 224 420000 500 ABB Control OFAF1H224 1
Three-phase supply voltage 380 V, 400 V or 415 V
-0040-3 69 1050 80 34500 500 ABB Control OFAF000H80 000
-0050-3 83 1480 100 63600 500 ABB Control OFAF000H100 000
-0060-3 100 1940 125 103000 500 ABB Control OFAF00H125 00
-0075-3 142 2400 160 200000 500 ABB Control OFAF00H160 00
-0070-3 138 2400 160 200000 500 ABB Control OFAF00H160 00
-0100-3 163 2850 200 350000 500 ABB Control OFAF1H200 1
-0120-3 198 3300 224 420000 500 ABB Control OFAF1H224 1
-0135-3 221 3820 250 550000 500 ABB Control OFAF1H250 1
-0165-3 254 4510 315 1100000 500 ABB Control OFAF2H315 2
-0205-3 286 4510 315 1100000 500 ABB Control OFAF2H315 2
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0050-5 64 1050 80 34500 500 ABB Control OFAF000H80 000
-0060-5 78 1480 100 63600 500 ABB Control OFAF000H100 000
-0070-5 95 1940 125 103000 500 ABB Control OFAF00H125 00
-0105-5 142 2400 160 200000 500 ABB Control OFAF00H160 00
-0100-5 121 2400 160 200000 500 ABB Control OFAF00H160 00
-0120-5 155 2850 200 350000 500 ABB Control OFAF1H200 1
-0140-5 180 2850 200 350000 500 ABB Control OFAF1H200 1
-0165-5 222 3820 250 550000 500 ABB Control OFAF1H250 1
-0205-5 256 4510 315 1100000 500 ABB Control OFAF2H315 2
-0255-5 286 4510 315 1100000 500 ABB Control OFAF2H315 2
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0050-7 52 740 63 28600 690 ABB Control OFAA0GG63 0
-0060-7 58 740 63 28600 690 ABB Control OFAA0GG63 0
-0070-7 79 1050 80 52200 690 ABB Control OFAA0GG80 0
-0100-7 91 1480 100 93000 690 ABB Control OFAA1GG100 1
-0120-7 112 1940 125 126000 690 ABB Control OFAA1GG125 1
-0145-7 131 2400 160 220000 690 ABB Control OFAA1GG160 1
-0175-7 162 2850 200 350000 690 ABB Control OFAA1GG200 1
-0205-7 186 3820 250 700000 690 ABB Control OFAA2GG250 2
PDM code:00096931-J, 00556489