Technical data
102
Cable entries
Brake resistor, mains and motor cable terminal sizes (per phase) and tightening
torques are given below
.
* 16 mm
2
rigid solid cable, 10 mm
2
flexible stranded cable
** with cable lugs 16...70 mm
2
, tightening torque 20...40 Nm. Cable lugs are not included in the delivery.
See page 64.
Dimensions, weights and noise
* Depth depends on the options included in the drive.
Frame
size
U1, V1, W1, U2, V2, W2, R+, R- Earthing PE
Maximum wire size Tightening torque Maximum wire size Tightening torque
mm
2
Nm mm
2
Nm
R2 up to 16 * 1.2...1.5 up to 10 1.5
R3 up to 16 * 1.2...1.5 up to 10 1.5
R4 up to 25 2…4 up to 16 3.0
R5 6...70 15 6...70 15
R6 95...185 ** 20...40 95 8
Frame size Height Width Depth* Weight Noise
mm mm mm kg dB
R2 370 165 193...226 8 62
R3 420 173 231.5...265 13 62
R4 490 240 252.2...271.5 24 62
R5 602 265 275.5 32 65
R6 700 300 399 64 65