Electrical installation
65
Frame size R6: Cable terminal installation [95 to 185 mm
2
(3/0 to 4/0 AWG)
cables]
Power cable protection
Frame size R5
Cover the power cable terminals as follows:
1. Cut holes for the installed cables into the clear plastic shroud.
2. Press the shroud onto the terminals.
a
b
PE
U1
U1
U1
V1
W1
U2
V2
W2
R-
UDC+
R+
UDC-
Input power cable
Motor cable
a. Connect the cable to the terminal.
b. Connect the terminal to the drive.
WARNING! If the wire size is less than
95 mm
2
(3/0 AWG), a cable lug must
be used. A cable of wire size less than
95 mm
2
(3/0 AWG) connected to this
terminal will loosen and may damage
the drive.
1
2
2