Planning the electrical installation
44
* manufactured before 1.1.1998
** For motors manufactured before 1.1.1998, check for additional instructions with the motor
manufacturer.
*** If the intermediate DC circuit voltage of the drive will be increased from the nominal level by resistor
braking or by the IGBT Supply Control Program (parameter selectable function), check with the
motor manufacturer if additional output filters are needed in the applied drive operation range.
N
O
N
-
A
B
B
Random-
wound and
form-wound
U
N
< 420 V Standard: Û
LL
=
1300 V
- + N or CMF + N + CMF
420 V < U
N
< 500 V Standard: Û
LL
=
1300 V
+ du/dt + du/dt + N + du/dt + N + CMF
or
+ du/dt + CMF
or
Reinforced:
Û
LL
= 1600 V,
0.2
microsecond
rise time
- + N or CMF + N + CMF
500 V < U
N
< 600 V Reinforced: Û
LL
= 1600 V
+ du/dt + du/dt + N + du/dt + N + CMF
or
+ du/dt + CMF
or
Reinforced:
Û
LL
= 1800 V
- + N or CMF + N + CMF
600 V < U
N
< 690 V Reinforced:
Û
LL
= 1800 V
+ du/dt + du/dt + N + du/dt + N + CMF
Reinforced:
Û
LL
= 2000 V,
0.3
microsecond
rise time ***
- N + CMF N + CMF
Manufacturer
Motor type Nominal mains
voltage (AC line
voltage)
Requirement for
Motor
insulation
system
ABB du/dt filter, insulated N-end bearing and ABB common
mode filter
P
N
< 100 kW
and
frame size < IEC
315
100 kW < P
N
<
350 kW or
frame size >
IEC
315
P
N
> 350 kW
or
frame size > IEC
400
P
N
< 134 HP
and frame size <
NEMA 500
134 HP < P
N
<
469 HP
or frame size >
NEMA 500
P
N
> 469 HP
or frame size >
NEMA 580