Parameters 305
Speed ref ramped 23.02 Speed ref ramp output (page 220). 11
Speed ref used 24.01 Used speed reference (page 226). 12
Torq ref used 26.02 Torque reference used (page 242). 13
Freq ref used 28.02 Frequency ref ramp output (page 250). 14
Process PID out 40.01 Process PID output actual (page 311). 16
Process PID fbk 40.02 Process PID feedback actual (page 311). 17
Process PID act 40.03 Process PID setpoint actual (page 311). 18
Process PID dev 40.04 Process PID deviation actual (page 311). 19
Other Source selection (see Terms and abbreviations on page 114). -
36.02 PVL filter time Defines a filtering time for the peak value logger. See
parameter 36.01 PVL signal source.
2.00 s
0.00 … 120.00 s Peak value logger filtering time. 100 = 1 s
36.06 AL2 signal source Selects the signal to be monitored by amplitude logger 2. The
signal is sampled at 200 ms intervals, and can be scaled
using parameter 36.07 AL2 signal scaling.
The results are displayed by parameters 36.40…36.49. Each
parameter represents an amplitude range, and shows what
portion of the samples fall within that range.
Amplitude logger 2 can be reset using parameter 36.09 Reset
loggers. The logger is also reset whenever the signal source
or scaling is changed. The date and time of the last reset are
stored into parameters 36.50 and 36.51 respectively.
Ambient
temperature
Zero None (amplitude logger 2 disabled). 0
Motor speed used 01.01
Motor speed used (page 117 ). 1
Output frequency 01.06 Output frequency (page 117). 3
Motor current 01.07 Motor current (page 117). 4
Motor torque 01.10 Motor torque (page 117 ). 6
DC voltage 01.11 DC voltage (page 117). 7
Power inu out 01.14 Output power (page 118). 8
Speed ref ramp in 23.01 Speed ref ramp input (page 220). 10
Speed ref ramped 23.02 Speed ref ramp output (page 220). 11
Speed ref used 24.01 Used speed reference (page 226). 12
Torq ref used 26.02 Torque reference used (page 242). 13
Freq ref used 28.02 Frequency ref ramp output (page 250). 14
Process PID out 40.01 Process PID output actual (page 311). 16
Process PID fbk 40.02 Process PID feedback actual (page 311). 17
Process PID act 40.03 Process PID setpoint actual (page 311). 18
Process PID dev 40.04 Process PID deviation actual (page 311
). 19
Ambient
temperature
01.70 Ambient temperature % (page 120).
The amplitude range of 0…100% corresponds to 0…60 °C or
32…140 °F.
20
Other Source selection (see Terms and abbreviations on page 114). -
36.07 AL2 signal scaling Defines the signal value that corresponds to 100% amplitude. 100.00
0.00 … 32767.00 Signal value corresponding to 100%. 1 = 1
No. Name/Value Description Def/FbEq16