Parameters 35
Parameter listing
No. Name/Value Description Def/
FbEq16/32
09
09 SPRS actual signals
Signals for monitoring SPRS operation.
These parameters are read-only.
09.01 Sync correction Shows output of the synchronization block.
This value is given by the parameter 77.04 Sync reference.
-
0...3000rpm Correction factor. 1 = 1rpm
09.02 Modified Sync
reference [%]
Shows modified synchronization reference of the
drive.
This value is same as the parameter 77.04 Sync reference
with scaling factor of speed.
-
0...3000% Value in percent. 1 = 1%
09.03 Speed actual [%] Shows output of the speed measurement block. -
0...1000% Value in percent. 1 = 1%
09.04 CCR speed
reference [%]
Shows speed reference from central control room (CCR). -
0...100% Value in percent. 1 = 1%
09.05 Speed reference
from CCR [%]
Shows speed reference from CCR modified internally in the
program.
-
0...100% Value in percent. 1 = 1%
09.06 SPRS Status word
1
Shows 15-bit data word for monitoring the output of speed
measurement block. This parameter is read-only.
-
Bit Name Description
0 Ack for SPRS contactor ON 1 = DI of SPRS contactor received /
acknowledged.
1 Ack for synchronized input 1 = DI of synchronized input received /
acknowledged.
2 Ack for GRR contactor ON 1 = DI of GRR contactor received /
acknowledged.
3 Ack for synchronized
contactor
1 = DI of synchronized contactor received /
acknowledged.
4 Ack for HT isolator ON 1 = DI of HT isolator received /
acknowledged.
5 Ack for LT isolator ON 1 = DI of LT isolator received /
acknowledged.
6 Ack for HT breaker ON 1 = DI of HT breaker received /
acknowledged.
7 Transformer healthy feedback
signal
1 = DI of transformer healthy feedback
received / acknowledged.
8...15 Reserved