38 Parameters
14
14 I/O extension
module 1
Configuration of I/O extension module 1 for SPRS.
For the SPRS application, Slot 2 must be used for the module
type FDIO-01. See parameters 14.01 and 14.02.
All the other configurations are similar to the ACS880 primary
control program.
15
15 I/O extension
module 2
Configuration of I/O extension module 2 for SPRS.
For the SPRS application, slot 3 must be used for the module
type FIO-11. See parameters 15.01 and 15.02.
All the other configurations are similar to the ACS880 primary
control program.
74
74 SPRS DI
Defines SPRS digital inputs.
74.01 ACK SPRS
contactor on
Defines the source from which DI SPRS contactor is
acknowledged.
DI1
Not selected 0 0
Selected 1 1
DI1 Digital input DI1. 2
DI2 Digital input DI2. 3
DI3 Digital input DI3. 4
DI4 Digital input DI4. 5
DI5 Digital input DI5. 6
DI6 Digital input DI6. 7
DI7 Digital input DI7. Used with FDIO-01. 8
DI8 Digital input DI8. Used with FDIO-01. 9
DI9 Digital input DI9. Used with FDIO-01. 10
DIO1 Digital input/output DIO1. 11
DIO2 Digital input/output DIO2. 12
DIIL Digital inputs DIIL. 13
Other Source selection (see Terms and abbreviations on page 34). -
74.02 ACK G/LRR
contactor on
Defines the source from which DI ROTOR contactor is
acknowledged.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
DI2
74.03 ACK Sync
contactor on
Defines the source from which DI SYNC contactor is
acknowledged.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
DI3
74.04 Sync input select Defines the source from which DI synchronized input is
acknowledged.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
DI5
74.05 SPRS/G(L) RR
select
Defines the source from which DI SPRS/GRR SEL done.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
DI6
No. Name/Value Description Def/