Parameters 39
74.06 HT isolator on
feedback
Defines the source from which DI HT Isolator on is
acknowledged.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
DI4
74.07 LT isolator on
feedback
Defines the source from which DI LT Isolator on is
acknowledged.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
DI9
74.08 Emergency stop
select
Defines the source from which DI emergency stop is
selected.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
DIIL
74.09 Transformer
healthy select
Defines the source from which DI feed back transformer
healthy is selected.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
Not selected
74.11 Fault reset Defines the source from which DI reset for SPRS is selected.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
Not selected
74.12 ACK HT breaker
select
Defines the source from which DI HT breaker on is
acknowledged.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
Not selected
74.13 Over current relay Defines the source from which DI over current relay input is
selected.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
Not selected
74.14 Speed increase Defines the source from which DI speed increase for SPRS is
selected.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
Not selected
74.15 Speed decrease Defines the source from which DI speed decrease for SPRS
is selected.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
Not selected
74.16 Rotor over voltage
select
Defines the source from which DI rotor over voltage for SPRS
is selected.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
Not selected
74.17 Earth fault select Defines the source from which DI earth fault for SPRS is
selected.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
Not selected
74.18 Control zone select Defines the source from which the DI control zone for SPRS
is selected.
If DI control zone = 1, the synchronization between inverter
output and rotor terminal voltage is enabled.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
Not selected
74.19 Application external
fault 1
Defines the source from which DI External Fault 1 for SPRS
is selected.
For the available selections, see parameter 74.01 ACK SPRS
contactor on.
Selected
No. Name/Value Description Def/
FbEq16/32