ControlMaster CM30 and CM50
Universal process controllers,
1
/4 and
1
/2 DIN 7 Advanced Level
IM/CM/ED–EN Rev. B 25
…Device Setup / …Basic Setup
Config Action The Config Action parameter is used to determine how the controller and controller
outputs behave when the Advanced level is entered – see page
24.
Continue
The controller continues to operate as in the operator level. Outputs continue to
operate as normal.
Hold
Puts the controller into Manual control mode.
When the Advanced level is exited, the controller returns to the pre-configuration mode
of operation.
Digital, relay and analog outputs are held at their value / state when configuration
mode is entered.
Inactive
Puts the controller into Manual control mode.
When the Advanced level is exited, the controller returns to the pre-configuration mode
of operation.
Digital and relay outputs are turned off.
Analog outputs are set to 0 mA.
Custom Template If this parameter is enabled, it enables the internal function blocks to be re-linked to
create custom configurations for special application requirements.
These sources are configured in Device Setup / Custom Config – see below.
Reset to Defaults Resets all configuration parameters to their default values.
Security Setup 3 Security access levels are provided, each protected by a password of up to 6
alphanumeric characters.
Note. Passwords Basic and Advanced level are not set at the factory and must be
entered by the end user(s).
Basic Password Basic level provides access to the Basic level parameters – see Section 6, page 18.
Advanced Password Provides access to all configuration parameters – see Section 7, page 24.
Reset Passwords Resets all passwords to factory values.
Custom Config
Loop 1 (2) PV
Sets the source for the process variable.
Loop 1 (2) Split O/P
Sets the source for output to the split output function block.
Loop 1 (2) Valve Mode
Sets the valve operation mode, Feedback or Boundless see page 21.
Loop 1 (2) Valve O/P
Sets the control input to the valve function block.
Loop 1 (2) Valve FB
Sets the source for position feedback input.
Loop 1 (2) TP OP1
Sets the source for control input to the time proportioning block for Output 1 – see
page
24.
Loop 1 (2) TP OP2
Sets the source for control input to the time proportioning block for Output 2 see page
24.
Loop 1 (2) RSP
Sets the source for the remote (external) setpoint.