EasyManua.ls Logo

ABB CM30 - Page 52

ABB CM30
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ControlMaster CM30 and CM50
Universal process controllers,
1
/4 and
1
/2 DIN 7 Advanced Level
50 IM/CM/ED–EN Rev. B
…Totalizer
Total DP’s Selects the number of decimal places displayed on the totalizer value.
Preset Count The value the totalizer counts from and the value applied when the totalizer is reset.
Predet Count The value at which the totalizer stops or wraps.
Intermed'te Count The value at which the intermediate count digital signal is activated. This can be used as
an alarm threshold to indicate when the Predet Count value is about to be reached.
Wrap Enable If set to On, the total is reset automatically to the Preset Count value once the Predet
Count value is reached. The wrap Digital signal is activated for 1 second.
If set to Off the count stops when the Predet Count value is reached. The wrap Digital
signal is activated until the totalizer is reset.
Reset Source The source required to reset the totalizer value. Selection is made on the rising edge.
Reset Days Selects the day or days to reset the totalizer.
Reset Hour Selects the hour to reset the totalizer (the totalizer is always reset exactly on the hour).
Reset

Table of Contents

Related product manuals