ControlMaster CM30 and CM50
Universal process controllers,
1
/4 and
1
/2 DIN 10 Specification
IM/CM/ED–EN Rev. B 75
Inputs
Thermocouple Maximum Range
°C (°F)
Accuracy
(% of reading)
B
#
–18 to 1800
(0 to 3270)
0.1 % or ±2 °C (3.6 °F)
(above 200 °C [392 °F]) *
E –100 to 900
(–140 to 1650)
0.1 % or ±0.5 °C
(0.9 °F)
J –100 to 900
(–140 to 1650)
0.1 % or ±0.5 °C
(0.9 °F)
K –100 to 1300
(–140 to 2350)
0.1 % or ±0.5 °C
(0.9 °F)
L –100 to 900
(–140 to 1650)
0.1 % or ±1.5 °C
(2.7 °F)
N –200 to 1300
(–325 to 2350)
0.1 % or ±0.5 °C
(0.9 °F)
R
#
–18 to 1700
(0 to 3000)
0.1 % or ±1 °C (1.8 °F)
(above 300 °C [540 °F])
S
#
–18 to 1700
(0 to 3000)
0.1 % or ±1 °C (1.8 °F)
(above 200 °C [392 °F])
T
#
–250 to 300
(–400 to 550)
0.1 % or ±0.5 °C (0.9 °F)
(above –150 °C [–238 °F])
#
For B, R, S and T thermocouples, accuracy is not guaranteed below the value stated.
RTD Maximum Range
°C (°F)
Accuracy
(% of reading)
PT100
–200 to 600
(–325 to 1100)
0.1 % or ±0.5 °C (0.9 °F)