DCS500 Pin and Parameter list
A 112
SIG6(LOAD SHARE)
Signal of FREE_SIGNALS-function block ( S2,S16/16 )
This block is containing signals which can be set by the CMT or panel.
Value which can be used to give control load sharing in master/follower drives. Before the
drive will use this value, it has to be connected to the load sharing input
SEL1.[LOAD_SHARE] (2403).
12521 FB_O: I2 SC: - HL: 30000 LL: -30000 D: 4000 U: -
SIG7(FLUX REF)
Signal of FREE_SIGNALS-function block ( S2,S16/16 )
This block is containing signals which can be set by the CMT or panel.
Value which can be used to give a flux reference. Before the drive will follow this
reference, it has to be connected to the flux reference input [FLUX_REF] (1002).
12522 FB_O: I2 SC: - HL: 30000 LL: -30000 D: 4095 U: -
SIG8(EMF REF)
Signal of FREE_SIGNALS-function block ( S2,S16/16 )
This block is containing signals which can be set by the CMT or panel.
Value which can be used to give an emf reference. Before the drive will follow this
reference, it has to be connected to the emf reference input [EMF_REF] (1003).
12523 FB_O: I2 SC: - HL: 30000 LL: -30000 D: 3786 U: -
SIG9(FORCE FWD)
Signal of FREE_SIGNALS-function block ( S2,S16/16 )
This block is containing signals which can be set by the CMT or panel.
Value which can be used to give a force command to field logic. Before the drive will
follow this command, it has to be connected to the force forward-input [F1_FORCE_FWD]
(1302).
12524 FB_O: B SC: - HL: 30000 LL: -30000 D: 0 U: -
SIG10(FORCE REV)
Signal of FREE_SIGNALS-function block ( S2,S16/16 )
This block is containing signals which can be set by the CMT or panel.
Value which can be used to give a force command to field logic. Before the drive will
follow this command, it has to be connected to the force reverse-input [F1_FORCE_REV]
(1303).
12525 FB_O: B SC: - HL: 30000 LL: -30000 D: 0 U: -
SIG11(CURR. REF)
Signal of FREE_SIGNALS-function block ( S2,S16/16 )
This block is containing signals which can be set by the CMT or panel.
Value which can be used to give a current reference. Before the drive will follow this
reference, it has to be connected to the current contoller input [CURR_REF] (402).
12526 FB_O: I2 SC: - HL: 30000 LL: -30000 D: 0 U: -
SIG12(CURR. STEP)
Signal of FREE_SIGNALS-function block ( S2,S16/16 )
This block is containing signals which can be set by the CMT or panel.
Value which can be used to give a current step. Before the drive will follow this step, it
has to be connected to the current contoller step input [CURR_STEP] (403).
12527 FB_O: I2 SC: - HL: 30000 LL: -30000 D: 0 U: -