H4T hardware
3ADW000803R0101 DCS880 H4T (Tosa) manual en a
Mains power connection
The H4T unit DCS880-S01-0630-07 can be connected to either an ND13 or to a dedicated transformer.
The H4T unit DCS880-S01-0590-08 must be connected to a dedicated transformer.
Line reactor type ND13 all busbars are 40 x 10:
Tightening torque
Torque [Nm]
ND13
M10
25
Dedicated transformer:
Only one unit is connected to the dedicated transformer.
No additional equipment is connected to the dedicated
transformer.
Typically for units size H4T.
Cooling fans
Fan assignment for DCS880
Converter type
Size
Configuration
Fan type
Airflow built in [m³/h]
DCS880-S01-0590-08
DCS880-S01-0630-07
H4T
4
1 x W2E200
230 V; 1
388
Fan cable sizes and tightening torque connected at the fan terminals
Fan terminals are X52 for H4T.
Converter type
Flexible cable
Solid cable
max [mm²]
torque [Nm]
max [mm²]
torque [Nm]
DCS880-S01-0590-08
DCS880-S01-0630-07
0.5 … 1.5
0.5 … 0.6
0.5 … 1.0
0.5 … 0.6
Cross-sectional areas - Tightening torques
Recommended cross-sectional area according to DINVDE 0276-1000 and DINVDE 0100-540 (PE) in a
trefoil arrangement, up to 50°C ambient temperature. The necessary wire torque at 60°C wire
temperature is the same as recommended in the following table.
Converter type
C1, D1
U1, V1, W1
PE
[Nm]
I
DC
[A-]
1
[mm
2
]
(2.)
[mm
2
]
I
V
[A~]
[mm
2
]
[mm
2
]
DCS880-S01-0590-08
590
2 x 120
-
484
2 x 120
1 x 120
1 x M12
50
DCS880-S01-0630-07
630
2 x 120
-
517
2 x 120
1 x 120
1 x M12
50

Other manuals for ABB DCS880

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB DCS880 and is the answer not in the manual?

ABB DCS880 Specifications

General IconGeneral
Control TypeDigital
Voltage RangeUp to 1200 V DC
Control PrincipleField-oriented control
Field SupplyIntegrated
Communication ProtocolsCANopen
CoolingAir
Protection ClassIP00, IP20, IP21, IP54
Protection FeaturesOvervoltage, overtemperature, short circuit, earth fault
Rated Voltage230 to 1200 V DC
Supply Voltage380 ... 690 V AC
Input Voltage Range230 to 690 V AC
Control ModeSpeed, Torque

Related product manuals