Error conditions
# LED indication Name of LED Colour
1 Green
2 Yellow
3 Green
4 Red
5 Yellow
1 2 3 4 5 Description of error Corrective action
1
Low voltage Check power supply (24 VDC ± 20%)
2
º º
Control logic fault Check that change-over switch bank 1
and bank 2 are equal.
Remove and reapply power. If error is
still present, contact your local ABB AB
JOKAB SAFETY distributor.
3
º º º
Error on safety outputs Check wiring of the OSSD outputs.
4
º º º
Muting lamp connection
fault or defective
Check the connection of the muting
lamp and/or check condition of the
muting lamp.
5
º
Mutual light interference Check the presence of ambient light
sources close to the protection eld.
Use coding option or remove the light
source.
6
º º
Error in oating blanking
mode. Object not present.
Check the position of the blanking
object. Make sure it is inside the
blanking area.
7
º º º º
EDM fault Check and correct EDM wiring.
8
º
Error in pre-reset mode Pre-reset condition was not met.
Correct placement of the pre-reset
switch to keep timing within the
specication.