2PAA118721 | Quick Installation Guide LD 810HSE Ex 9
Electrostatic aspects must be considered when mounting the Linking
Devices. Electrostatic charges have to be prevented.
In explosion group IIC and Zone 2 no protected plastic surfaces > 20 cm
2
are allowed; in IIB or dust-Ex, 100 cm
2
may be reached.
The hazard of any objects falling onto a Linking Device must be
prevented.
The Linking Device does not meet the requirements of impact protection
and IP54 (according to IEC 60529). It must be installed in a protective
enclosure which meets the requirements for resistance to impact and IP
as stated in section 26.4 of IEC/EN 60079-0. This enclosure must be fully
mounted and intact. If the enclosure is damaged, the operation is not
permitted.
The Linking Device is defined as instruments and apparatus of low energy
according to clause 23 of IEC/EN 60079-15; thus the requirement stated
in sub-clause C limiting the transient characteristic to 40 % above the
rated voltage has to be adhered to when mounting the equipment.
When removing the packaging ensure that no dirt can enter the enclosure
or the plugs.
If any vibration during the operation may cause parts of the plugs to
loosen, the plugs have to be provided with a light firm varnish used for
securing screws. An extraction force of 0.5 Nm has to be achieved at an
equivalent thread.
To circuits of Zone 2 only such equipment may be connected that is
suitable for operation in this zone and has been certified accordingly.
Components may only be replaced by original spare parts that are also
approved for the use in Ex -atmospheres. Spare parts are ordered as