DescriptionExample
value
NameIndex
Sets the digital input that is connected
to the secondary input of the STO
function.
DI X113:4
& X114:4
STO input BSTO.12
Note: In a non-redundant system, you
can use a one-channel input (for ex-
ample, DI X113:4).
Sets the time after which the drive can
restart when the FSO module has activ-
ated the STO function and opened the
drive STO circuit. With this parameter,
you can let the drive restart before the
motor has stopped (fly-start). This
parameter is applicable only if the STO
function is requested from STO input
A (STO.11) or STO input B (STO.12).
2000 msRestart delay
after STO
STO.13
STO function: Adjust the value when
necessary. If you do not want to use
the fly-start feature, set this parameter
to the same value as parameter
STO.14.
Parameter settings 57